Description
Stenner Pump Model S3407
Stenner S3407 Specs:- 40 Gallons per Day Output
- Pump Tube # 7
- Turndown 4-20mA - 100:1
- Turndown Manual Mode - 20:1
- Flow activated by 4-20mA analog signal
- Scalable 25% to 100%
- Robust enclosed housing,
- NEMA 4X rated
- Leak detection
- Backup pump capability
- Remote start or stop
- LED Indicators
- Three dedicated output relays
- 2-year warranty
What is included with the S3404 Pump Model?
3x Connecting Nuts 1/4" or 3/8"
3x Ferrules 1/4"
1x Injection fitting 25 psi (1.7 bar) max.
1x Weighted suction line strainer 1/4" or 3/8"
1x 20' Roll of suction/discharge tubing 1/4" or 3/8", white, UV black
1x Additional pump tube
2x Additional latches
1x Mounting bracket
1x Manual
Key Industries:
- Industrial and municipal wastewater treatment facilities
- Municipal Water Treatment
- Process Water Applications
Additional Applications
- Disinfectants,Oxidizing Agents, Acids, and alkalines.
- Injection of liquid biocides in cooling towers
- Corrosion, scale, and algae control on plumbing fixtures and water supply equipment Metering additives specific to a manufacturing process
- Will the Stenner S3407 pump hold up to chromic acid with a pH of <1 and a temperature of 130 F?
- The S3407 has a maximum operating temperature of 104 F. The pump has a “B†rating for chromic acid less than 50% which means the fluid can have minor to moderate effects.
Due to the “B†rating on the pump tube and such a high temperature rating we would not recommend this application.